Characteristic / Application
Pressure transmitter for pressure or hydrostatic level measurement with flush mounted metallic CONTITE measuring cell:
- hermetically welded
- absolute condensation tight
- climate-resitant
- long-term stable
- Lowest temperature influences
Cable version with suspension clamp -
Specialities
Modularity to differential pressure and process pressure devices (replacable display, universal electronics)
diagnostic functions
Hermetically sealed Contite measuring cell (condensate-resistant and climatic-proofed) -
Supply / Communication
4...20mA HART:
10,5...45V DC
Ex ia: 10,5...30V DC
PROFIBUS PA /
FOUNDATION Fieldbus:
9...32V DC (Non Ex) -
Accuracy
Standard 0,2%
Optional 0,1% -
Long term stability
0,05% of URL/year
-
Ambient temperature
-40°C...85°C
(-40°F...185°F) -
Process temperature
PE cable: -10°C…70°C / 14°F…158°F
FEP cable: -10°C…80°C / 14°F…176°F -
Process pressure absolute / max. overpressure limit
40 bar (600 psi)
-
Pressure measuring range
100mbar...10bar
(1.5psi...150psi) -
Main wetted parts
Alloy C
316L
Cable (PE/FEP)
optional coating AuPt
optional coating AuRh -
Process connection
Mounting clamp
-
Max. measurement distance
100m (328ft) H2O
-
Communication
4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus -
Certificates / Approvals
ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI
-
Safety approvals
SIL
-
Design approvals
EN10204-3.1
NACE MRO175 -
Marine approval
GL/ ABS/ LR/ BV/ DNV
-
Drinking water approvals
KTW/ NSF/ ACS
-
Options
Initial device settings
Overvoltage protection -
Application limits
If pressurized, usage of two pressure transmitters to measure the differential pressure (electronic dP)
Observe ratio head pressure : hydrostatic pressure